In accordance with Safety Rules in Russia, the restrictions on application of local control stations with EExe and 2EExed type of protection are in force for Zone 1, application of local control stations with Exd type of protection is required. Explosion-proof local control stations and indicating devices series PKIVA is a reliable control and signaling equipment for hazardous zone 0 (only in intrinsically safe version 0Ex ia IIC или 0Ex ia I), zone 1 (without limitations as per Safety Rules).
Each individual product undergoes thorough acceptance in accordance with accurate quality control plan GOST R ISO 9001-2015 (ISO 9001:2015). Compliance with norms and technical specifications of the customer is verified in accordance with special procedure. inspections are carried out stepwise throughout the entire production cycle. Local control stations are produced according to the latest European and Russian technology, and their price can compete even with outdated samples produced in Russia.
Ready standard modular Exd local control stations are highly resistant to hydrogen sulphide which is confirmed by TR CU certificates. Service life of flameproof joints of Exd explosion-proof enclosures is more than 25 years. One of the distinctive features of explosion-proof equipment produced by "ZAVOD GORELTEX" Co. Ltd. is ergonomic design of control, indicating and signaling elements. Large size of control elements makes it possiple to work in gloves (which is important for outdoor operation at low temperatures). Indicating elements have large diameter (40 mm) and are equipped with reflector, which makes the signal clearly visible at large viewing angle and various degrees of surface dirtiness. A wide range of control, indicating and signaling elements of standard version are offered, a version upon customer’s request can also be produced.
Full production cycle starting from casting molds and to ready product is performed at the explosion-proof equipment plant “ZAVOD GORELTEX” Co. Ltd. on the territory of the Russian Federation.
Scope of application - hazardous indoor and outdoor areas in accordance with explosion protection marking, GOST 30852.13-2002 (IEC 60079-14:1996) and areas hazardous with combustible dust ignition, as per GOST IEC 61241-3-2011, dangerous production facilities of I, II, III, IV hazard classes under supervision of Rostekhnadzor and national supervisory bodies of the CU and the CIS countries.
Technical Regulation TR CU 010/2011 "On the safety of machinery and equipment.
Annex 1. General regulations of safety machines and equipment. Clause 15 :
«…Control devices of a machine and (or) equipment must be constructed so that their form, sizes and contact surfaces of the user correspond to a capture way (fingers, hand) or pressing (hand finger, palm, foot)…»
For the equipment intended for operation at ambient temperatures below zero or in aggressive environment, control elements of the equipment must be of larger size, since the user operates the equipment in protective gloves. It is prohibited to use the control elements that do not meet this requirement.
Marking for order
|
Description
|
Drawing
|
PKIVA011 |
- Enclosure type PKIVA-X; |
|
PKIVA021 |
- Enclosure type PKIVA-X; - Momentary button KGV01K11 red 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
|
PKIVA031 |
- Enclosure type PKIVA-X; - Momentary button KGV01Z11 green 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1kg |
|
PKIVA071 |
- Enclosure type PKIVA-X; - Locking mushroom button, unlocking by rotation KGV07, red, 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
|
PKIVA091 |
- Enclosure type PKIVA-X; - Locking mushroom button, unlocking with key KGV09, red, 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
|
PKIVA111 |
- Enclosure type PKIVA-X; - Signal lamp LGV01Z, green, base ВА9s - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
|
PKIVA131 |
- Enclosure type PKIVA-X; - Signal lamp LGV01ZH, amber, base ВА9s - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
|
PKIVA151 |
- Enclosure type PKIVA-X; - Signal lamp LGV01К, red, base ВА9s - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
|
PKIVA231 |
- Enclosure type PKIVA-X; - Signal lamp LGV01S, blue, base ВА9s - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
|
PKIVA171 |
- Enclosure type PKIVA-X; - Indicating button green KGV06Z, 1NO+1NC, lamp base ВА9s - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
|
PKIVA191 |
- Enclosure type PKIVA-X; - Indicating button amber KGV06ZH, 1NO+1NC, lamp base ВА9s - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
|
PKIVA211 |
- Enclosure type PKIVA-X; - Indicating button red KGV06K, 1NO+1NC, lamp base ВА9s - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1 kg |
Marking for order
|
Description
|
Drawing
|
PPG011 |
- Enclosure type PPG 25A; |
|
PPG031 |
- Enclosure type PPG 25A; |
|
PPG051 |
- Enclosure type PPG 25A; |
Marking for order
|
Description
|
Drawing
|
PKIVA301 |
- Enclosure type PKIVA-XX; - Momentary button KGV01CH11 black 1NO+1NC - 1 pc.; - Momentary button KGV01K11 red 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.5 kg |
|
PKIVA321 |
- Enclosure type PKIVA-XX; - Momentary button KGV01Z11 green 1NO+1NC - 1 pc.; - Momentary button KGV01K11 red 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.5 kg |
|
PKIVA341 |
- Enclosure type PKIVA-XX; - Momentary button KGV01Z11 green 1NO+1NC - 1 pc.; - Locking mushroom button, unlocking by rotation KGV07, red, 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.5 kg |
|
PKIVA361 |
- Enclosure type PKIVA-XX; - Momentary button KGV01CH11 black 1NO+1NC- 1 pc.; - Locking mushroom button, unlocking by rotation KGV07, red, 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.5 kg |
|
PKIVA381 |
- Enclosure type PKIVA-XX; |
|
PKIVA401 |
- Enclosure type PKIVA-XX; |
|
PKIVA421 |
- Enclosure type PKIVA-XX; |
|
PKIVA441 |
- Enclosure type PKIVA-XX; |
|
PKIVA461 |
- Enclosure type PKIVA-XX; |
|
PKIVA481 |
- Enclosure type PKIVA-XX; |
Marking for order
|
Description
|
Drawing
|
PKIVA501 |
- Enclosure type PKIVA-XXX; - Momentary button KGV01CH11 black 1NO+1NC - 1 pc.; - Momentary button KGV01K11 red 1NO+1NC - 1 pc.; - Momentary button KGV01CH11 black 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.9 kg |
|
PKIVA521 |
- Enclosure type PKIVA-XXX; - Momentary button KGV01Z11 green 1NO+1NC - 1 pc.; - Momentary button KGV01К11 red 1NO+1NC - 1 pc.; - Momentary button KGV01Z11 green 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.9 kg |
|
PKIVA541 |
- Enclosure type PKIVA-XXX; - Signal lamp LGV01Z, green , base ВА9s - 1 pc.; - Momentary button KGV01CH11 black 1NO+1NC - 1 pc.; - Momentary button KGV01К11 red 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.9 kg |
|
PKIVA561 |
- Enclosure type PKIVA-XXX; - Signal lamp LGV01Z, green, base ВА9s - 1 pc.; - Momentary button KGV01Z11 green 1NO+1NC - 1 pc.; - Momentary button KGV01К11 red 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.9 kg |
|
PKIVA581 |
- Enclosure type PKIVA-XXX; - Signal lamp LGV01K, red, base ВА9s - 1 pc.; - Momentary button KGV01CH11 black 1NO+1NC - 1 pc.; - Momentary button KGV01K11 red, 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.9 kg |
|
PKIVA601 |
- Enclosure type PKIVA-XXX; - Momentary button KGV01CH11 black 1NO+1NC - 1 pc.; - Locking mushroom button, unlocking by rotation KGV07, red, 1NO+1NC - 1 pc.; - Momentary button KGV01CH11 black 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.9 kg |
|
PKIVA621 |
- Enclosure type PKIVA-XXX; - Indicating button KGV06K red, 1NO+1NC, lamp base ВА9s - 1 pc.; - Momentary button KGV01Z11 green 1NO+1NC - 1 pc.; - Momentary button KGV01ZH11 yellow 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.9 kg |
|
PKIVA641 |
- Enclosure type PKIVA-XXX; - Indicating button yellow KGV06ZH, 1NO+1NC, lamp base ВА9s - 1 pc.; - Momentary button KGV01K11 red 1NO+1NC - 1 pc.; - Momentary button KGV01S11 blue 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.9 kg |
|
PKIVA661 |
- Enclosure type PKIVA-XXX; - Indicating button blue KGV06S, 1NO+1NC, lamp base ВА9s - 1 pc.; - Momentary button KGV01ZH11 yellow 1NO+1NC - 1 pc.; - Momentary button KGV01К11 red 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 1.9 kg |
Marking for order
|
Description
|
Drawing
|
PKIVA701 |
- Enclosure type PKIVA-XX + PKIVA-XX; |
|
PKIVA721 |
- Enclosure type PKIVA-XX + PKIVA-XX; |
*Encapsulation and grounding of armor are carried out outside of cable gland. Inner sheath is subject to insertion into cable gland.
Marking for order
|
Описание
|
Чертеж
|
PKIV701 |
- Enclosure type PKIVA-XXXX; |
|
PKIV711 |
- Enclosure type PKIVA-XXXXX; - Signal lamp LGV01Z, green, base ВА9s - 1 pc.; - Momentary button KGV01CH11 black 1NO+1NC - 3 pcs.; - Locking mushroom button, unlocking by rotation KGV07, red, 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 3.5 kg |
|
PKIV721 |
- Enclosure type PKIVA-XXXXXX; - Signal lamp LGV01Z, green, base ВА9s - 1 pc.; - Momentary button KGV01CH11 black 1NO+1NC - 4 pcs.; - Locking mushroom button, unlocking by rotation KGV07, red, 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 4.5 kg |
|
PKIV731 |
- Enclosure type PKIVA-XXXXXXX; - Signal lamp LGV01Z, green, base ВА9s - 1 pc.; - Momentary button KGV01CH11 black 1NO+1NC - 5 pcs.; - Locking mushroom button, unlocking by rotation KGV07, red, 1NO+1NC - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 4.5 kg |
Marking for order
|
Description
|
Drawing
|
KV-KIP011 |
- Enclosure type KV-KIP; - Ammeter (scale..) - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 2 kg |
|
KV-KIP031 |
- Enclosure type KV-KIP; - Voltmeter (scale..) - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 2 kg |
|
KV-KIP051 |
- Enclosure type KV-KIP; - Ohmmeter (scale..) - 1 pc.; - cable gland for non-armored cable KNV2MNK/R, cable diameter 6-18 mm* - 1 pc.; - Ambient temperature, °С: -60...+40/+55 - Mass 2 kg |
|
|