Fitting joints series RZV (EYS)

+
x
<
>
Fitting joints series RZV (EYS)PURPOSE AND SCOPE OF APPLICATION

Partition fittings with encapsulation with PG-COMPOUND are applied in electrical conduit for the arrangement of partition seals of separate sections during installation in electrical conduit and carrying out local leakage tests in the electrical conduit.

Separation of sections of the electrical conduit using fittings with encapsulation with PG-COMPOUND ensures prevention of ingress of combustible gases, vapors or flame from one part of Exd conduit section to another.

Partition fitting encapsulated with compound shall be installed as close as possible to Exd enclosures of distribution boxes, boards, control cabinets, light fixtures. Partition fittings are used for the separation of each internal volume of a separate Exd enclosure and from the enternal space of electrical conduit.

For the provision of explosion protection, the cable shall be separated to the conductors and partition fittings shall be encapsulated with PG-COMPOUND. The fitting is filled with non-flammable glass fiber in order to prevent running out of the compound before its curing.

Partition fittings with encapsulation with PG-COMPOUND are intended for the prevention of transfer of the explosive mixture through the pipe from one room to another, for the transition between areas and also for the division and separation of the internal volumes of the explosion-proof equipment. Special function of the partition fittings is that they prevent ingress of fire to the pipes with cables.

Partition fittings prevent distribution of gas, vapors and fire in the electrical conduit.

RZV - vertical partition fitting joint

Scope of application - hazardous indoor and outdoor areas in accordance with explosion protection marking, GOST 30852.13-2002 (IEC 60079-14:1996) and areas hazardous with combustible dust ignition, as per GOST IEC 61241-3-2011, dangerous production facilities of I, II, III, IV hazard classes under supervision of Rostekhnadzor and national supervisory bodies of the CU and the CIS countries.

+
CONFORMITY TO STANDARDS IN RUSSIA
ГОСТ Р МЭК 60079-0-2011, ГОСТ 30852.0-2002 (МЭК 60079-0:1998), ГОСТ 30852.1-2002 (МЭК 60079-1:1998), ТР ТС 012/2011, ГОСТ 14254-96 (МЭК 529-89), Гл. 7.3 ПУЭ, Гл. 7.4 ПУЭ
+
CERTIFICATES
Маркировка взрывозащиты Marking:
1Ex db IIC Gb
1Ex e IIC Gb
2Ex nR IIC Gc
Ex tb IIIC Db
Ex db IIC Gb U
Ex e IIC Gb U
Ex nR IIC Gc U
Ex tb IIIC Db U
Mining equipment marking:
РВ Ex db I Mb
РП Ex e I Mc
Ex db I Mb U
Ex e I Mc U
+
TECHNICAL DATA
Ambient temperature, °С:
-75/-60...+135
Thread:
Material:
Corrosion-resistant modified aluminum silicon alloy, resistant to salt spray and other chemical substances including hydrogen sulfide and hydrochloric acid vapors, resistant to saline and acidic pit waters, frictionally intrinsically safe
Filling:
Compound PG-COMPOUND
Climatic version:
NF1 (upon request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.1, W5)
+
DIMENSIONS, OPTIONS, ACCESSORIES
MARKING
External surface coating as per customer’s specification
/RAL (___)
Marine version
/MORE
Compound PG-COMPOUND
/PG-KOMPAUND
Glass fiber
/SV
+
OVERALL AND MOUNTING DIMENSIONS
Габаритные и присоединительные размеры РЗВ
Dimension type F Amount of compound, g A, mm B, mm Mass, kg
RZV1G 1/2" 35 70 56 0,1
RZV2G 3/4" 50 85 72 0,1
RZV3G 1" 100 90 73,5 0,2
RZV4G 1 1/4" 240 110 91,5 0,25
RZV5G 1 1/2" 240 109,5 91,5 0,3
RZV6G 2" 380 129 110 0,4
RZV7G 2 1/2" 1250 162 135,5 0,5
RZV8G 3" 1350 175 149 0,8
RZV10G 4" 1450 185 175,5 1,1
+
FORMATION OF MARKING
RZV   X / Х  – TU 3400-007-72453807-07






          Type of element
          Dimension type
          Options, accessories and versions

EXAMPLE: RZV8R-TU 3400-007-72453807-07

+