Explosion-proof flexible single phase constant wattage heating cable GTG-KABEL2 (RETO-CORD/RD2-RD4)

+
x
<
>
Explosion-proof flexible single phase constant wattage heating cable GTG-KABEL2 (RETO-CORD/RD2-RD4)PURPOSE AND SCOPE OF APPLICATION

Explosion-proof flexible heating cable of constant power is intended for heating and maintaining the process temperature of automation objects, tanks, pipelines and any other objects that require additional protection against freezing and icing.

The explosion-proof constant wattage heating cable delivers constant power output over the entire length of the heating surface. Heating cables of parallel type with constant power output are intended for electrical heating in industrial conditions of pipelines and equipment. They can also be used for process temperature maintenance and frost protection where high heat output and / or high temperature resistance is required.

A parallel heating element is located inside the constant wattage heating cable. The heating element consists of a high resistance alloy heating coil wrapped around two parallel conductors. The distance between the points of contact of the conductors determines the length of the heating zone. The parallel design allows you to cut the cable into pieces of the required length and terminate the cable directly on site. As the temperature rises, the output power of the heating cable decreases. The cable's relatively flat temperature curve provides relatively low inrush current and high power output at elevated temperatures.

1. Conductive tinned copper conductors.
2. Insulation.
3. Nichrome wire.
4. Internal insulation.
5. External insulation.
6. Aluminium-magnesium alloy protective braid.
7. Outer protective shell.

For better heat transfer, it is recommended to use an assembly sealant.

Scope of application - explosion hazardous areas of premises and outdoor installations, in accordance with the assigned explosion protection marking, the requirements of GOST IEC 60079-14-2013 and industry safety rules governing the use of this equipment in hazardous areas.

+
CONFORMITY TO STANDARDS IN RUSSIA
ГОСТ 14254-96 (МЭК 529-89), ГОСТ 30852.0-2002 (МЭК 60079-0:1998), ГОСТ Р МЭК 62086-1-2003, ГОСТ 30852.8-2002 (МЭК 60079-0:1998), ГОСТ Р МЭК 60079-31-2010, ТР ТС 012/2011, ТР ТС 004/2011, ГОСТ IEC 61241-1-1-2011, ГОСТ 24754-2013, Гл. 7.3 ПУЭ, Гл. 7.4 ПУЭ, ГОСТ 30852.20-2002
+
CERTIFICATES
Маркировка взрывозащиты Marking:
1Ex e IIC Т5...T3 Gb X
Ex tb IIIC T95°C...T185°C Db X
Protection:
+
TECHNICAL DATA
Ambient temperature, °С:
-60...+75
Power, W:
15, 30, 40, 60
Operating position in space:
Any
Supply voltage:
~220 V (50/60 Hz)
Electrical protection degree of insulation:
~2000 V, 50Hz during 1 min
Climatic version:
NF1 (upon request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.1, W5)
+
DIMENSIONS, OPTIONS, ACCESSORIES
MARKING
Cable element for heating cable end termination
/GTG-ZGK
Non-explosion-proof version
/PROM
+
OVERALL AND MOUNTING DIMENSIONS
Technical data for heating cables type GTG-KABEL2
Type GTG-KABEL2-90-15 GTG-KABEL2-120-30 GTG-KABEL2-150-40 GTG-KABEL2-180-60
Power, W/m 15±10% 30±10% 40±10% 60±10%
Maximum maintained temperature, °C +(90±5) +(120±10) +(150±10) +(180±10)
Maximum allowable temperature without load (1000 hours in total) +205 +205 +205 +205
Nominal cable size, mm 6,8 х 8,6 6,8 х 8,6 6,8 х 8,6 6,8 х 8,6
Maximum length of heating section at ambient temperature -20°C, m 1 1 1 1
Temperature class Т5/Т95°C Т4/Т125°C Т3/Т155°C Т3/Т185°C
Cable sheath material Fluorinated ethylene propylene Fluorinated ethylene propylene Fluorinated ethylene propylene Fluorinated ethylene propylene
Minimum installation temperature, °C -60 -60 -60 -60
Maximum circuit length when using type "C" circuit breakers in accordance with EN 60898 at 230V
Dimensions of electrical protection installation Switch-on temperature, °C Maximum heating cable length per circuit (m) at 230V AC
GTG-KABEL2-90-15 GTG-KABEL2-120-30 GTG-KABEL2-150-40 GTG-KABEL2-180-60
16A (-20°C) 200 90 60 40
(+10°C) 200 90 60 40
25A (-20°C) 330 150 110 70
(+10°C) 330 150 110 70
32A (-20°C) 440 210 150 100
(+10°C) 440 210 150 100
40A (-20°C) 540 270 195 120
(+10°C) 540 270 195 120

Diagram of dependence of linear power on temperature

Diagram of dependence of linear power on temperature

+
FORMATION OF MARKING
GTG-KABEL2 - Х - Х - Х / Х – TU 28.21.13-041-72453807-2017
Type of device
Temperature, °C: 90, 120, 150, 180
Power, W: 15, 30, 40, 60
Length in meters
Options, accessories and versions

Example: GTG-KABEL2-120-30-30-TU 28.21.13-041-72453807-2017

+