Explosion-proof cable glands KOVZ (FECA/CP) for encapsulation for armored cable

+
x
<
>
Explosion-proof cable glands KOVZ (FECA/CP) for encapsulation for armored cablePURPOSE AND SCOPE OF APPLICATION

Explosion-proof cable glands KOVZ for encapsulation for armored cable are used in places where ingress and explosion protection are required. They secure the cable from accidental pulling out. KOVZ explosion-proof cable glands provide a barrier for armored cable.

Explosion-proof bushing for encapsulation gives the possibility to use the cable gland for insertion of non-armored cables with non-circular cross-section or having the structure where the wires do not adjoin tightly.

The structure of encapsulated bushing consists of two elements: a sleeve and a release element. Two-component epoxy composition that is included in the scope of supply is used as a sealant. The main advantage of this composition compared to liquid compound is its plasticity, which is good for mounting of cable in cable gland. Apart from plasticity, the epoxy composition ensures high bonding strength, it does not shrink, as well as it is resistant to water, oils and solvents.

Increased wall thickness of GORELTEX cable glands bodies considerably enhances their strength compared with cable glands of other manufacturers.

KOVZ cable gland may be used for direct insertion as a part of fireproof enclosures of IIA, IIB+H2, IIC subgroups, which have the volume exceeding 2000 cm3.

KOVZ explosion-proof cable glands are completely suitable for use with equipment having ExnR marking.

Clamping ring of the armor helps to use KOVZ cable gland for all types of cable armor/braid: wire armor, with braid, tape armor. Clamping ring of the armor helps to crimp armor/braid with the thickness from 0 to 3.5 mm (KOVZ01-...-KOVZ5 from 0 to 2.5 mm, starting from KOVZ6 from 0 to 3.5 mm). External sealing ring for ingress protection prevents ingress of water into cable gland, which can cause damage to armor/braid.

KOVZ explosion-proof cable glands ensure earthing circuit continuity between cable armor/braid and cable gland body by means of clamping ring of the armor/braid that ensures protection against electromagnetic disturbances.

Thanks to their design, KOVZ explosion-proof cable glands ensure cable unloading, protection against pulling out without causing damage to the structure of cable sheath and conductors, as well as prevent cable overcompression.

Scope of application – outdoor and indoor hazardous areas as per explosion protection marking, GOST 30852.13-2002 (IEC 60079-14:1996), dangerous production facilities of I, II, III, IV hazard class supervised by Rostechnadzor of the RF and national technical supervision bodies of the Customs Union and CIS countries.

+
CONFORMITY TO STANDARDS IN RUSSIA
ГОСТ 14254-96 (МЭК 529-89), ГОСТ 30852.10-2002 (МЭК 60079-11:1999), ГОСТ 30852.14-2002, ГОСТ 30852.0-2002 (МЭК 60079-0:1998), ГОСТ 30852.8-2002 (МЭК 60079-0:1998), ГОСТ 30852.1-2002 (МЭК 60079-1:1998), ГОСТ Р МЭК 60079-0-2011, ТР ТС 004/2011, ТР ТС 012/2011, РД 5.2-093-2004, ГОСТ IEC 60079-1-2011, Гл. 7.3 ПУЭ, Гл. 7.4 ПУЭ, ГОСТ 24754-2013, ГОСТ 30852.20-2002
+
CERTIFICATES
Маркировка взрывозащиты Marking:
1Ex db IIC Gb
1Ex e IIС Gb
2Ex nR IIС Gc
Ex tb IIIC Db
Mining equipment marking:
РВ Ex db I Mb
РП Ex e I Mc
РН1, РН2
+
TECHNICAL DATA
Ambient temperature, °С:
-60...+185
-60…+130 (for 1Ex d IIC Gb)
Material:
Nickel-plated brass resistant to vapor of hydrogen sulphide, hydrochloric acid and sea fog NK code
Stainless steel grade 08Х18Н10 as per GOST 5632-2014 (AISI 304) N code
Climatic version:
NF1 (upon request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.1, W5)
+
DIMENSIONS, OPTIONS, ACCESSORIES
MARKING
External seal for ingress protection (IP) on thread (cylindrical and metric thread)
/UKF
Locknut (cylindrical and metric thread)
/KG
Grounding ring
/A31
Stainless steel grade 03Х17Н13М2 as per GOST 5632-2014 (316L)
/316L
Marine version
/MORE
Non-explosion-proof version
/PROM
+
OVERALL AND MOUNTING DIMENSIONS
Габаритные и присоединительные размеры КОВЗ
Standard explosion-proof cable glands KOV(FECA/CP), metric thread GOST 24705
Cable gland dimension type Thread, GOST 24705 Dimensions, mm Diameter of crimped cable, mm Mass, kg
all files
Main Alternative АС1 АС2 ØМ С øD, mm øD1, mm ød, mm
KOVZ1M FECA/CP1I M20 x 1,5 26 26 28.5 83 9 - 17 13,5 10 0,15
KOVZ2M FECA/CP2I M25 x 1,5 34 34 38 96 15 - 25 19 15 0,27
KOVZ3M FECA/CP3I M32 x 1,5 40 40 44,5 106 21 - 31 25.5 23 0,37
KOVZ4M FECA/CP4I M40 x 1,5 50 50 56 103 27 - 37 32 26.5 0,57
KOVZ5M FECA/CP5I M50 x 1,5 57 60 67 111,5 36 - 46 39 35,5 0,92
KOVZ6M FECA/CP6I M63 x 1,5 68 70 77 121,5 45 - 53 47 43,5 1,41
KOVZ7M FECA/CP7I M75 x 1,5 80 80 88 124 52 - 65 55 51,5 1,8

Standard explosion-proof cable glands KOV (FECA/CP), taper inch thread NPT
Cable gland dimension type Thread, NPT Dimensions, mm Diameter of crimped cable, mm Mass, kg
Main Alternative АС1 АС2 ØМ С øD, mm øD1, mm ød, mm
KOVZ1N FECA/CP1N 1/2" 26 26 28.5 85 9 - 17 13,5 10 0,19
KOVZ2N FECA/CP2N 3/4" 34 34 38 98 15 - 25 19 15 0,31
KOVZ3N FECA/CP3N 1" 40 40 44,5 115 21 - 31 25.5 23 0,42
KOVZ4N FECA/CP4N 1 1/4" 50 50 56 110 27 - 37 32 26.5 0,62
KOVZ5N FECA/CP5N 1 1/2" 57 60 67 119 36 - 46 39 35,5 0,94
KOVZ6N FECA/CP6N 2" 68 70 77 131 45 - 53 47 43,5 1,45
KOVZ7N FECA/CP7N 2 1/2" 80 80 88 134 52 - 65 55 51,5 2,0

Number of wires pulled through cable gland (calculated under outlet Ød). Core cross-section, mm2

Cable gland dimension type Thread, NPT Number of wires pulled through cable gland (calculated under outlet Ød). Core cross-section, mm2
Main Alternative 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150
KOVZ1N FECA/CP1N 1/2" 13 8 6 5 4 2 1 - - - - - - -
KOVZ2N FECA/CP2N 3/4" 31 20 14 11 9 5 3 1 1 1 - - - -
KOVZ3N FECA/CP3N 1" 73 47 34 26 22 11 8 4 4 2 1 1 - -
KOVZ4N FECA/CP4N 1 1/4" 97 62 45 35 30 15 11 5 5 3 2 1 1 1
KOVZ5N FECA/CP5N 1 1/2" 174 111 82 62 54 27 20 10 10 6 4 3 2 1
KOVZ6N FECA/CP6N 2" 262 168 123 94 81 42 30 15 15 10 6 5 3 2
KOVZ7N FECA/CP7N 2 1/2" 368 235 173 132 114 58 45 21 21 14 9 7 4 3

Number of wires pulled through cable gland (calculated under outlet Ød). Core cross-section, mm2
Cable gland dimension type Thread, GOST 24705 Number of wires pulled through cable gland (calculated under outlet Ød). Core cross-section, mm2
Main Alternative 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150
KOVZ1M FECA/CP1I M20 x 1,5 13 8 6 5 4 2 1 - - - - - - -
KOVZ2M FECA/CP2I M25 x 1,5 31 20 14 11 9 5 3 1 1 1 - - - -
KOVZ3M FECA/CP3I M32 x 1,5 73 47 34 26 22 11 8 4 4 2 1 1 - -
KOVZ4M FECA/CP4I M40 x 1,5 97 62 45 35 30 15 11 5 5 3 2 1 1 1
KOVZ5M FECA/CP5I M50 x 1,5 174 111 82 62 54 27 20 10 10 6 4 3 2 1
KOVZ6M FECA/CP6I M63 x 1,5 262 168 123 94 81 42 30 15 15 10 6 5 3 2
KOVZ7M FECA/CP7I M75 x 1,5 368 235 173 132 114 58 45 21 21 14 9 7 4 3
+
FORMATION OF MARKING
KOVZ   X   Х   Х  /  Х  – TU 3400-007-72453807-07
                  Cable gland type
                  Dimension type
                  Thread type: Taper inch NPT - N; Metric GOST 24705 - M;
Taper pipe GOST  6211-81 - R; Pipe cylindrical GOST 6357-81 - G
                  Cable gland material: Nickel-plated brass - NK, Stainless steel - N
                  Options, accessories and versions

Example:
KOVZ1NNK -TU 3400-007-72453807-07
- Cable type: armored
- Thread: 1/2 “ taper inch NPT
- Material: nickel-plated brass
+
+