Explosion-proof circuit breaker-disconnector-fuse SHGVA-VRP пare intended for switching, protective disconnection and overcurrent protection of the load in low-voltage circuits in hazardous areas of the facilities of chemical, oil processing, gas and other branches of industry in areas with potentially explosive atmosphere. Explosion-proof circuit breaker-disconnector-fuse SHGVA-VRP are made on the base of SHORVA enclosures.
Operating handle of SHGVA-VRP can be sealed.
DISCONNECTION:
- Disconnection of both outputs of fuse links in circuit breakers of all ratings. Quick-acting mechanism of disconnection independent from the fuses.
- Complete disconnection of power circuits for control and assurance of safety of people and equipment.
- Auxiliary contacts GS1 AN.
- Positive opening of contacts in case of contact welding.
- Clearly visible circuit break between open contacts (visible if the enclosure with window is used).
- Category of application ~23/690 V and 23/500 V.
PROTECTION:
- With fuses type gG (gl).
- With fuses type aM (together with overload heat relay).
- With quick-break fuses.
- Indicator of fuse trip (visible if the enclosure with window is used).
- Conventional maximum short circuit current of 100 kA for circuit breakers of all ratings.
- Breaking capacity of fuses is equivalent to the maximum breaking capacity of disconnector switches.
Full production cycle starting from casting molds and to ready product is performed at the explosion-proof equipment plant “ZAVOD GORELTEX” Co. Ltd. on the territory of the Russian Federation.
Scope of application - hazardous indoor and outdoor areas and mines non-hazardous with gas or dust, in accordance with explosion protection marking, GOST 30852.13-2002 (IEC 60079-14:1996) and areas hazardous with combustible dust ignition, as per GOST IEC 61241-3-2011, dangerous production facilities of I, II, III, IV hazard classes under supervision of Rostekhnadzor and national supervisory bodies of the CU and the CIS countries.
For explosion-proof mining version mining junction boxes with Exd type of protection are used.
Name | Number of poles | Rated current, A | Dimension type of fuse-link | Dimensions, mm (not including cable glands) | Mass, kg: | ||
A | B | C | |||||
SHGVA-VRP-3P-32-… | 3 | 32 | C… | 235 | 235 | 164 | 8,5 |
SHGVA-VRP-3P+N-32-… | 4 | 32 | C… | 235 | 235 | 164 | 8,5 |
SHGVA-VRP-3P-50-… | 3 | 50 | E… | 276,5 | 276,5 | 218 | 12,5 |
SHGVA-VRP-4P-50-… | 4 | 50 | E… | 276,5 | 276,5 | 218 | 12,5 |
SHGVA-VRP-3P-100-… | 3 | 100 | F… | 276,5 | 276,5 | 218 | 12,5 |
SHGVA-VRP-4P-100-… | 4 | 100 | F… | 429,5 | 429,5 | 291 | 36,6 |
SHGVA-VRP-3P-160-… | 3 | 160 | G… | 429,5 | 429,5 | 291 | 36,6 |
SHGVA-VRP-4P-160-… | 4 | 160 | G… | 429,5 | 429,5 | 291 | 36,6 |
SHGVA-VRP | - | X | - | XХ | - | Х | - | X | / | X | – TU 3400-005-72453807-07 |
Device type |
|||||||||||
Number of poles | |||||||||||
Rated current of fuse-link | |||||||||||
Type of fuse-link | |||||||||||
Type of cable gland (side of location) | |||||||||||
Options, accessories and versions |
EXAMPLE OF ORDER: SHGVA-VRP-3P-250-HA1201-1KOV4(B)-1KNV5(G) – TU 3400-005-72453807-07
Explosion-proof switch-disconnector-fuse on the base of SHORVA enclosure, 3 poles, rated current 250 A with fuse-link 200A for protection against short circuit current with one cable gland for armored cable KOV4 on side B and one cable gland KNV5 on side D.
Dimension type and type of fuse-link | Rated voltage, V | Rated current, A | Protection against | |
short circuit | overload | |||
C… (cylindrical 10х38) | ~ 500 |
0,16 0,25 |
СА001 | - |
0,25 | СА002 | - | ||
0,5 | СА005 | - | ||
1 | СА01 | - | ||
2 | СА02 | СN02 | ||
4 | СА04 | СN04 | ||
6 | СА06 | СN06 | ||
8 | СА08 | СN08 | ||
10 | СА10 | СN10 | ||
12 | СА12 | СN12 | ||
16 | СА16 | СN16 | ||
~400 | 20 | СА20 | СN20 | |
25 | СА25 | СN25 | ||
32 | СА32 | СN32 | ||
E… (cylindrical 14х51) | ~690 | 0,25 | ЕА002 | - |
0,5 | ЕА005 | - | ||
~ 500 | 1 | ЕА01 | - | |
2 | ЕА02 | - | ||
4 | ЕА04 | ЕN04 | ||
6 | ЕА06 | ЕN06 | ||
8 | ЕА08 | - | ||
10 | ЕА10 | ЕN10 | ||
12 | ЕА12 | - | ||
16 | ЕА16 | ЕN16 | ||
20 | ЕА20 | ЕN20 | ||
25 | ЕА25 | ЕN25 | ||
32 | ЕА32 | ЕN32 | ||
40 | ЕА40 | ЕN40 | ||
~ 400 | 50 | ЕА50 | ЕN50 | |
F… (cylindrical 22х58) | ~690 | 4 | FА04 | - |
6 | FА06 | - | ||
8 | FА08 | - | ||
10 | FА10 | FN10 | ||
16 | FА16 | - | ||
20 | FА20 | FN20 | ||
25 | FА25 | FN25 | ||
32 | FА32 | FN32 | ||
40 | FА40 | FN40 | ||
50 | FА50 | FN50 | ||
~ 500 | 63 | FA63 | FN63 | |
80 | FA80 | FN80 | ||
100 | FA100 | FN100 | ||
G… (prismatic with knife blade contacts) | ~ 500 | 50 | GA1051 | GN1051 |
63 | GA1061 | GN1061 | ||
80 | GA1081 | GN1081 | ||
100 | GA1101 | GN1101 | ||
125 | GA1121 | GN1121 | ||
160 | GA1161 | GN1161 | ||
H… (prismatic with knife blade contacts) | ~ 500 | 160 | HA1161 | HN1161 |
200 | HA1201 | HN1201 | ||
250 | HA1251 | HN1251 | ||
J… (prismatic with knife blade contacts) | ~ 500 | 250 | JA1251 | JN1251 |
315 | JA1311 | JN1311 | ||
400 | JA1401 | JN1401 | ||
K… (prismatic with knife blade contacts) | ~ 500 | 400 | KA1401 | - |
500 | KA1501 | KN1501 | ||
630 | KA1631 | KN1631 | ||
L… (prismatic with knife blade contacts) | ~ 500 | 630 | LA1631 | - |
800 | LA1801 | LN1801 | ||
1000 | LA1101 | LN1101 | ||
~ 400 | 1250 | LA1251 | LN1251 |
Previous international name "ZAVOD GORELTEX" Co. Ltd. TU 3400-005-72453807-07 |
The Customs Union name "ZAVOD GORELTEX" Co. Ltd. TU 3400-005-72453807-07 |
CCA-VRP-3Р-32-… | SHGVA-VRP-3P-32-… |
CCA-VRP-3Р+Nc-32-… | SHGVA-VRP-3P+N-32-… |
CCA-VRP-3Р-50-… | SHGVA-VRP-3P-50-… |
CCA-VRP-4Р-50-… | SHGVA-VRP-4P-50-… |
CCA-VRP-3Р-100-… | SHGVA-VRP-3P-100-… |
CCA-VRP-4Р-100-… | SHGVA-VRP-4P-100-… |
CCA-VRP-3Р-160-… | SHGVA-VRP-3P-160-… |
CCA-VRP-4Р-160-… | SHGVA-VRP-4P-160-… |
CCA-VRP-3Р-250-… | SHGVA-VRP-3P-250-… |
CCA-VRP-4Р-250-… | SHGVA-VRP-4P-250-… |