Explosion-proof power board UVR (CCFE) (10kV)
PURPOSE AND SCOPE OF APPLICATION
Explosion-proof high-voltage power boards are made in the form of suspending structure consisting of the main enclosure and indicating enclosure connected with each other. Explosion-proof boards are equipped with a voltage indication device.
For direct insertion of cables and wires to Exd enclosure, the following specially developed Exd glands for direct insertion with sealing are applied: KNV, KOV, KNVTN, KNVTV, KNVM series and with encapsulation KNVZ series. According to the mandatory requirements, this characteristic is specified in the certificate. This helps to refuse from inlet junction box (except for mining version РВ), which makes the products of "ZAVOD GORELTEX" Co. Ltd. unique compared with products of other companies.
IT IS IMPORTANT TO KNOW : Some "garage" manufacturers from different countries assemble switching modules (Exd type of protection) with direct insertion, installing ordinary Exd cable glands (no data in certificates). These products are EXPLOSIVE, since these glands do not ensure flame protection in case of aging of sealing.
Scope of application – outdoor and indoor hazardous areas of I, II, III, IV hazard classes as per explosion protection marking, GOST 30852.13-2002 (IEC 60079-14:1996), regulating application of electrical equipment in hazardous areas and areas with presence of combustible dust as per GOST 61241-3-2011.
X sign placed after Ex marking indicates that it is prohibited to use the device in hazardous mixtures of acetylene with air.
Marking:
1Ex db IIС T6...T4 Gb X
1Ex db IIB+H
2 T6...T4 Gb
Ex tb IIIC T85°С...T135°С Db
Certificates and permits:
TU 3400-005-72453807-07
TU 27.12.31-048-72453807-2017
Ambient temperature, °С:
-60...+40/+55
Maximum voltage, V:
10000
Rated current, A:
up to 600
Electric shock hazard protection class:
I
Climatic version:
NF1 (upon request NF2, NF3, NF4, NF5, F1, F2, F3, F5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.1, W5)
OVERALL AND MOUNTING DIMENSIONS
Note: high voltage boards are customizable.
OPTIONS, ACCESSORIES AND VERSIONS
ORDER CREATION
Installation on frame
/RAMA
Heating for automation
/OBOGREV
Internal thermal insulation
/TEPLOIZOLJCIJA
External surface coating as per customer’s specification
/RAL (___)
Acceptance by customer
/PRIEMKA
Earthquake-resistant version
/MSK-64
Version for tropics with protection against bugs
/TERMITY
Drain plug for condensate removal
/DKUV
Anti-condensation coating
/AP
GOST 14254-96 (IEC 529-89), GOST R IEC 60079-0-2011, GOST IEC 60079-1-2011, TR CU 012/2011, GOST IEC 61241-1-1-2011, Ch. 7.3 PUE, Ch. 7.4 PUE, RD 5.2-093-2004, GOST R IEC 60079-31-2010