Transition cable element series RKN-ZK (TP) with threaded joint

+
+
x
<
>
Transition cable element series RKN-ZK (TP) with threaded jointPURPOSE AND SCOPE OF APPLICATION

Explosion-proof transition cable elements are intended for the connection of flat or round electrical wires or optic cables between two enclosures of the explosion-proof equipment, usually between an Exd-enclosure and input Exe enclosure, or between two Exd enclosures. Actual range of operating temperatures is determined by the applied type of the wires or a cable. More detailed information for certain types is provided upon request. Partition nipple-barriers could be manufactured with hook-up wires (conductor), with coaxial cables (coaxial), with optic cables (optic), with flat wires, with clamping screw (bolted) as per the order.

Upon customer‘s request, stranded gas migration preventing heat-resistant hook-up wires  for partition fittings with completely encapsulated internal space.

Scope of application - hazardous indoor and outdoor areas in accordance with explosion protection marking, GOST 30852.13-2002 (IEC 60079-14:1996), dangerous production facilities of I, II, III, IV hazard classes under supervision of Rostekhnadzor and national supervisory bodies of the CU and the CIS countries.

+
CONFORMITY TO STANDARDS IN RUSSIA
ГОСТ 30852.0-2002 (МЭК 60079-0:1998), ГОСТ 30852.1-2002 (МЭК 60079-1:1998), ГОСТ 14254-96 (МЭК 529-89), Гл. 7.3 ПУЭ, Гл. 7.4 ПУЭ, ТР ТС 012/2011
+
CERTIFICATES
Маркировка взрывозащиты Marking:
Ex db IIC Gb U
Ex tb IIIC Db U
Mining equipment marking:
Ex db I Mb U
Protection:
+
TECHNICAL DATA
Ambient temperature, °С:
-60...+180
Material:
Nickel-plated brass code NK
Galvanized steel code О
Stainless steel grade 08Х18Н10 as per GOST 5632-2014 (AISI 304) code N
Filling:
Climatic version:
NF1 (upon request NF2, NF3, NF4, NF5, F1, F2, F3, F5, MU1, MU2, MU3, MU4, W2.1, W5)
+
DIMENSIONS, OPTIONS, ACCESSORIES
MARKING
Anaerobic sealant PG-REZBA-G
/PG-REZBA-G
Marine version
/MORE
Locknut (cylindrical and metric thread)
/KG
+
OVERALL AND MOUNTING DIMENSIONS
Переходной кабельный элемент серии РКН-ЗК

Type of fitting Diameter, mm H, mm L, mm h, mm AС, mm S, mm
RKN-ZK 10 30 15 9 14 16,5
12 16 19
16 20 23,5
20 27 32,2
24 28 32,5
25 30 34,5
32 36 40
33 36 42
36 40 46,5
38 42 48,5
42 45 52
+
FORMATION OF MARKING
RKN-ZK  -  X   X ( X x Х ) Х  – TU 27.33.13-031-72453807-2017












                      Type of the element
                      Diameter
                      Material
                      Number of wires
                      Cross-section of the wires
                      Length of free wire ends, dm

EXAMPLE: RKN-ZK-10N(3x2.5)2 - TU 27.33.13-031-72453807-2017
- Through insulator with threaded connection, sealed with compound,
- connecting thread M10,
- material stainless steel,
- 3 wires with a cross-section of 2.5 mm,
- length of free wire ends 2 dm.

Non-standard nipple-barriers can be produced as per customer‘s layout

+